North American monitoring of a hotel with room size GSHPS (ground-source heat pump system).

Summary

The 149-room lake front hotel has a ground loop that is partially incorporated into the building's structural pilings and a heat pump water heating system that is integrated into the ground loop of the space conditioning system. Loop temperatures are ranging between 4 and 27 °C across the year. The integration of the water heating heat pumps into the system reduced the summer heat rejection loads by more than 15%. Variable speed loop pumping dramatically reduced system energy use by 92% compared to a conventional constant speed pumping system. This system demonstrates the performance benefits of geothermal heat pump systems.

Details

  • Original title: North American monitoring of a hotel with room size GSHPS (ground-source heat pump system).
  • Record ID : 2001-0483
  • Languages: English
  • Source: Heat pump systems for single-room applications. Workshop proceedings.
  • Publication date: 1998/06/17
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles from the proceedings (10)
See the conference proceedings