Système cryogénique utilisant l'azote liquide sous-refroidi pour le refroidissement d'un câble de puissance à supraconducteur haute température.

Cryogenic system with the sub-cooled liquid nitrogen for cooling HTS power cable.

Auteurs : FAN Y. F., GONG L. H., XU X. D., et al.

Type d'article : Article

Résumé

A 10-m long, three-phase AC high-temperature superconducting (HTS) power cable has been fabricated and tested in China August 2003. The sub-cooled liquid nitrogen (LN2) was used to cool the HTS cable. The sub-cooled LN2 circulation was built by means of a centrifugal pump through a heat exchanger in the sub-cooler, the three-phase HTS cable cryostats and a LN2 gas-liquid separator. The LN2 was cooled down to 65 K by means of decompressing, and the maximum cooling capacity was about 3.3 kW and the amount of consumed LN2 was about 72 L/h at 1500 A. Cryogenic system design, test and some experimental results are presented in this paper.

Détails

  • Titre original : Cryogenic system with the sub-cooled liquid nitrogen for cooling HTS power cable.
  • Identifiant de la fiche : 2005-2417
  • Langues : Anglais
  • Source : Cryogenics - vol. 45 - n. 4
  • Date d'édition : 04/2005

Liens


Voir d'autres articles du même numéro (3)
Voir la source