Document IIF

Système de contrôle à ultrasons de l'écoulement du R134a et du R600a dans un circuit frigorifique.

Ultrasound monitoring of flowing R134a and R600a inside a refrigerant circuit.

Auteurs : MONTICELLI E., PECORARI C., MERLI F., et al.

Résumé

The equipment utilizes ultrasonic waves and temperature measurements to detect liquid accumulation of the refrigerant in points of particular interests within the evaporator and at the expansion device inlet. In correspondence of the accumulation points, the time of flight of the ultrasound waves inside the cavity is measured and therefore the temporal evolution of the refrigerating system in terms of oil/refrigerant mixture is given. The relationship between concentration, speed of sound and temperature has been determined for R134a and R600a.

Documents disponibles

Format PDF

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Ultrasound monitoring of flowing R134a and R600a inside a refrigerant circuit.
  • Identifiant de la fiche : 2000-1341
  • Langues : Anglais
  • Source : 20th International Congress of Refrigeration: Refrigeration into the Third Millennium.
  • Date d'édition : 19/09/1999

Liens


Voir d'autres communications du même compte rendu (447)
Voir le compte rendu de la conférence