Système de pompe à chaleur à l'ammoniac à haute efficacité pour l'eau des procédés industriels utilisant le concept ISEC. 1.

Highly efficient ammonia heat-pump system for industrial process water using the ISEC concept. 1.

Numéro : pap. ID48

Auteurs : ROTHUIZEN E. D., MADSEN C., ELMEGAARD B., et al.

Résumé

The purpose of the Isolated System Energy Charging (ISEC) is to provide a high-efficient ammonia heat pump system for hot water production. The ISEC concept uses two storage tanks for the water, one discharged and one charged. The charged tank is used for the industrial process while the discharged tank, is charging. Charging is done by circulating the water in the tank through the condenser several times and thereby gradually heats the water. This result in a lower condensing temperature than if the water was heated in one step. A dynamic model of the system, implemented in Dymola, is used to investigate the performance of the ISEC system. The ISEC concept approaches the efficiency of a number of heat pumps in series and the COP of the system may reach 6.8, which is up to 25 % higher than a conventional heat pump heating water in one step.

Documents disponibles

Format PDF

Pages : 8 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Highly efficient ammonia heat-pump system for industrial process water using the ISEC concept. 1.
  • Identifiant de la fiche : 30013168
  • Langues : Anglais
  • Source : 11th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2014). Proceedings. Hangzhou, China, August 31-September 2, 2014.
  • Date d'édition : 02/08/2014

Liens


Voir d'autres communications du même compte rendu (119)
Voir le compte rendu de la conférence