Document IIF
Système de pompe à chaleur à l'ammoniac à haute efficacité pour l'eau des procédés industriels utilisant le concept ISEC. 1.
Highly efficient ammonia heat-pump system for industrial process water using the ISEC concept. 1.
Numéro : pap. ID48
Auteurs : ROTHUIZEN E. D., MADSEN C., ELMEGAARD B., et al.
Résumé
The purpose of the Isolated System Energy Charging (ISEC) is to provide a high-efficient ammonia heat pump system for hot water production. The ISEC concept uses two storage tanks for the water, one discharged and one charged. The charged tank is used for the industrial process while the discharged tank, is charging. Charging is done by circulating the water in the tank through the condenser several times and thereby gradually heats the water. This result in a lower condensing temperature than if the water was heated in one step. A dynamic model of the system, implemented in Dymola, is used to investigate the performance of the ISEC system. The ISEC concept approaches the efficiency of a number of heat pumps in series and the COP of the system may reach 6.8, which is up to 25 % higher than a conventional heat pump heating water in one step.
Documents disponibles
Format PDF
Pages : 8 p.
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Highly efficient ammonia heat-pump system for industrial process water using the ISEC concept. 1.
- Identifiant de la fiche : 30013168
- Langues : Anglais
- Source : 11th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2014). Proceedings. Hangzhou, China, August 31-September 2, 2014.
- Date d'édition : 02/08/2014
Liens
Voir d'autres communications du même compte rendu (119)
Voir le compte rendu de la conférence
-
Ammonia heat pump for energy saving in food ind...
- Auteurs : PANNO G., AUGUANNO S., MESSINEO A., et al.
- Date : 06/05/2005
- Langues : Anglais
- Source : Ammonia Refrigerating Systems, Renewal and Improvement.
- Formats : PDF
Voir la fiche
-
Energy saving. 90°C hot water NH3 heat pumps in...
- Auteurs : BOONE J.
- Date : 12/06/2015
- Langues : Anglais
- Source : Le ultime tecnologie del freddo e del condizionamento. Atti del 16° Convegno Europeo: June 12-13, 2015, Milano, Italia.
- Formats : PDF
Voir la fiche
-
Development of an industrial high temperature h...
- Auteurs : HE Y., YANG D., CAO F., et al.
- Date : 14/07/2014
- Langues : Anglais
- Source : 2014 Purdue Conferences. 15th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Groundwater system with ammonia heat pumps save...
- Auteurs : WINTHER H., KLOOTWIJK M.
- Date : 12/04/2010
- Langues : Anglais
- Source : 9th IIR-Gustav Lorentzen Conference on Natural Working Fluids (GL2010). Proceedings. Sydney, Australia, April 12-14, 2010.
- Formats : PDF
Voir la fiche
-
Sistema de aguas subterráneas con bombas de cal...
- Auteurs : WINTHER H., KLOOTWIJK M.
- Date : 01/2011
- Langues : Espagnol
- Source : IIF-IIR/Frío Calor Aire acond. - vol. 39 - n. 432
- Formats : PDF
Voir la fiche