Système frigorifique au CO2 pour grandes surfaces pour les climats chauds.

CO2 supermarket refrigeration system for hot climates.

Résumé

CO2 single compression cycle is severely penalised when the hot sink temperature approaches the critical temperature; in this situation COP improvement can be obtained with a modified thermodynamic cycle. Parallel compression is a well known method to enhance efficiency and it was already considered as a possible solution for above 0°C supermarket refrigeration purposes. In this paper a theoretical analysis shows how it can actually be a realistic way for commercial refrigeration in hot climates. Technological aspects of multi-compressor systems with independent parallel compressors, as the volume ratio control between main compressors and parallel compressors are faced. The integration with water spray on gas cooler or evaporative cooling can further improve efficiency. Six-month data from a recent installation in Europe are presented, thus demonstrating that this solution is efficient, and it is also mature from a technological point of view so that it can be implemented when necessary.

Documents disponibles

Format PDF

Pages : 2010-2

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : CO2 supermarket refrigeration system for hot climates.
  • Identifiant de la fiche : 2010-1173
  • Langues : Anglais
  • Source : 9th IIR-Gustav Lorentzen Conference on Natural Working Fluids (GL2010). Proceedings. Sydney, Australia, April 12-14, 2010.
  • Date d'édition : 12/04/2010

Liens


Voir d'autres communications du même compte rendu (84)
Voir le compte rendu de la conférence