Tour de refroidissement humide à convection naturelle : comparaison d'un modèle asymétrique en 2 dimensions obtenu fondé sur la dynamique numérique des fluides avec un modèle unidimensionnel.

Comparison of a 2D axisymmetric CFD model of a natural draft wet cooling tower and a 1D model.

Auteurs : WILLIAMSON N., BEHNIA M., ARMFIELD S.

Type d'article : Article

Résumé

The performance predictions of a simple one-dimensional natural draft wet cooling tower model and a two-dimensional axisymmetric numerical model are compared under a range of design parameters. The two-dimensional model has the ability to resolve radial non-uniformities across the tower which the one-dimensional model only computes as a bulk averaged value. The difference between the overall cooling range predicted by the two models is generally less than 2%, with no divergence in the agreement between the methods with respect to any design parameter. [Reprinted with permission from Elsevier. Copyright, 2007].

Détails

  • Titre original : Comparison of a 2D axisymmetric CFD model of a natural draft wet cooling tower and a 1D model.
  • Identifiant de la fiche : 2008-2086
  • Langues : Anglais
  • Source : International Journal of Heat and Mass Transfer - vol. 51 - n. 9-10
  • Date d'édition : 05/2008

Liens


Voir d'autres articles du même numéro (7)