Document IIF

Transfert de chaleur lors de l'ébullition dans un tube avec insert en forme d'étoile.

Boiling heat transfer in an evaporator tube with a star-shaped insert.

Résumé

A test facility was modified to provide the means for R22 measurements on a four-meter evaporator tube equipped with a ten channel star-shaped insert. The purpose of the work is to investigate the applicability of heat transfer and pressure drop correlations derived for smooth tubes for this kind of inserts. Different correlations for the calculation of heat transfer and pressure drop were used. The only adjustment due to different geometry is the implementation of the tube's hydraulic diameter. It was found that the calculated heat transfer was between 30 and 50% higher than the measured, while pressure drop was calculated to more or less 3% of the measured values. Possible causes are discussed.

Documents disponibles

Format PDF

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Boiling heat transfer in an evaporator tube with a star-shaped insert.
  • Identifiant de la fiche : 2000-1243
  • Langues : Anglais
  • Source : 20th International Congress of Refrigeration: Refrigeration into the Third Millennium.
  • Date d'édition : 19/09/1999

Liens


Voir d'autres communications du même compte rendu (447)
Voir le compte rendu de la conférence