Transfert de chaleur suite à l'assèchement d'un frigorigène en écoulement dans des tubes horizontaux des évaporateurs.

[In Japanese. / En japonais.]

Auteurs : MORI H., YOSHIDA S., KAKIMOTO Y., et al.

Type d'article : Article

Résumé

The heat transfer coefficient at medium and high mass flow rates in the smooth tube was lower than the single-phase heat transfer coefficient of the superheated vapour flow, of which mass flow rate was given on the assumption that the flow was in a thermodynamic equilibrium. A prediction method of post-dryout heat transfer coefficient was developed to reproduce the measurement satisfactorily for the smooth tube. The post-dryout heat transfer in the micro-fin tube can be regarded approximately as a superheated vapour single-phase heat transfer.

Détails

  • Titre original : [In Japanese. / En japonais.]
  • Identifiant de la fiche : 2001-2676
  • Langues : Japonais
  • Source : Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers - vol. 17 - n. 4
  • Date d'édition : 2000