Post-dryout heat transfer to a refrigerant flowing in horizontal evaporator tubes.

[In Japanese. / En japonais.]

Author(s) : MORI H., YOSHIDA S., KAKIMOTO Y., et al.

Type of article: Article

Summary

The heat transfer coefficient at medium and high mass flow rates in the smooth tube was lower than the single-phase heat transfer coefficient of the superheated vapour flow, of which mass flow rate was given on the assumption that the flow was in a thermodynamic equilibrium. A prediction method of post-dryout heat transfer coefficient was developed to reproduce the measurement satisfactorily for the smooth tube. The post-dryout heat transfer in the micro-fin tube can be regarded approximately as a superheated vapour single-phase heat transfer.

Details

  • Original title: [In Japanese. / En japonais.]
  • Record ID : 2001-2676
  • Languages: Japanese
  • Source: Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers - vol. 17 - n. 4
  • Publication date: 2000
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles in this issue (8)
See the source