TRANSFERT DE MASSE DE CONTAMINANTS SURSATURES DANS DES ECHANGEURS THERMIQUES CRYOGENIQUES A HELIUM.

MASS TRANSFER OF SUPERSATURATED CONTAMINANTS IN CRYOGENIC HELIUM HEAT EXCHANGERS.

Auteurs : CHANG H. M., SMITH J. L. Jr

Type d'article : Article

Résumé

UNE TECHNIQUE EXPERIMENTALE EST DEVELOPPEE POUR MESURER LA DISTRIBUTIONDE GIVRE ACCUMULE DANS LE PASSAGE D'UN ECHANGEUR THERMIQUE CRYOGENIQUE A HELIUM. LE GIVRE EST ACCUMULE PAR CONDENSATION D'UN CONTAMINANT SUR LA PAROI PENDANT L'OPERATION D'ECOULEMENT PERMANENT DE L'ECHANGEUR A CONTRE-COURANT. QUAND LE DEGRE DE SURSATURATION EST FAIBLE, LA DISTRIBUTION D'ACCUMULATION S'ACCORDE AVEC LA SOLUTION ANALYTIQUE SANS FORMATION DE NEIGE. QUAND LA SURSATURATION AUGMENTE, UN PIC SECONDAIRE NET EST OBSERVE DANS LA DISTRIBUTION A CAUSE DE LA FORMATIONDE NEIGE DANS L'ECOULEMENT LIBRE ET DE SON DEPOT SUR LA PAROI. UNE CONDITION EST FORMULEE POUR LA FORMATION EN NEIGE D'UN CONTAMINANT SURSATURE DANS L'HELIUM.

Détails

  • Titre original : MASS TRANSFER OF SUPERSATURATED CONTAMINANTS IN CRYOGENIC HELIUM HEAT EXCHANGERS.
  • Identifiant de la fiche : 1991-0120
  • Langues : Anglais
  • Source : International Journal of Heat and Mass Transfer - vol. 33 - n. 6
  • Date d'édition : 06/1990

Liens


Voir d'autres articles du même numéro (1)
Voir la source