Un nouveau système frigorifique à éjection muni d'une pompe à jet supplémentaire.

A new ejector refrigeration system with an additional jet pump.

Auteurs : YU J., CHEN H., REN Y., et al.

Type d'article : Article

Résumé

A new ejector refrigeration system (NERS) with an additional liquid-vapour jet pump was proposed. The jet pump was used to decrease the back pressure of the ejector, and then the entrainment ratio and the COP of the new system could be increased. The theoretical analysis and simulation calculation was carried out for the new system. The comparison between NERS and the conventional ejector refrigeration system (ERS) was made under the same operating condition. The variation of the new system's COP with generator temperature and back pressure was discussed for two refrigerants: R134a and R152a. The calculation results show the COP of NERS can be improved more effectively and that happens at the cost of more pump work. From the point of view of exergy, the new system is of higher exergetic efficiency and feasible. [Reprinted with permission from Elsevier. Copyright, 2005].

Détails

  • Titre original : A new ejector refrigeration system with an additional jet pump.
  • Identifiant de la fiche : 2006-1766
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 26 - n. 2-3
  • Date d'édition : 02/2006

Liens


Voir d'autres articles du même numéro (6)
Voir la source