Une étude comparative entre un système de conditionnement d'air à vitesse constante et un système à vitesse variable.

A comparative study between a constant-speed air conditioner and a variable-speed air conditioner.

Auteurs : CHEN I. Y., CHEN Y. M., CHANG Y. J., et al.

Résumé

This study compares the performance between a constant-speed air conditioner and a variable-speed air conditioner subject to identical operation conditions. Influences of added heat load, ambient temperature, and setting point temperature on the system performances had been examined. The results show that the average consumed power is increased with the increase of heat load and with the decrease of T(set). Also, the variable-speed AC consumes less average power than that of the constant-speed AC under the same heat load and T(set). For the same initial room temperature, the constant-speed AC can reach setting point earlier. Although the variable-speed AC takes a longer time to reach the set point temperature, its compressor operates at a low speed operation as T(set) reached. Thus, the consumed power is reduced in the long term operation and the room set point temperature can be maintained at a more stable condition than the constant-speed AC.

Détails

  • Titre original : A comparative study between a constant-speed air conditioner and a variable-speed air conditioner.
  • Identifiant de la fiche : 2009-2463
  • Langues : Anglais
  • Source : ASHRAE Transactions. Papers presented at the 2009 ASHRAE Winter Conference: Chicago, Illinois, January 2009. Volume 115, part 1.
  • Date d'édition : 25/01/2009