Document IIF

Une étude comparative sur la performance optimale de cycles frigorifiques au R410A et au R32.

A comparative study on the optimum performance of R410A and R32 refrigeration cycles.

Numéro : pap. n. 283

Auteurs : SHIH Y. C., SHIAH Y. S., HOUNG Y. H., et al.

Résumé

The optimum performance of R410A and R32 refrigeration cycles is studied in this paper. A theoretical model for the coefficient of performance is derived first. Then, the L9(34) orthogonal table of Taguchi method is used for performance analysis. In the experimental design, four factors and three levels are considered. The range of each factor is given as: 0.8~1.0 MPa for evaporator pressure, 2.1~2.7 MPa for condenser pressure, 0~10°C for degree of superheating, and 0~10°C for degree of subcooling. Finally, a predicted model of COP is proposed for both R410A and R32 systems. According to the response table and ANOVA table, two significant factors contributed to COP are found as evaporator pressure and condenser pressure. Meanwhile, the optimum COP calculated from predicted model has a good agreement with the data of cycle theory. In addition, the value of optimum COP is 1% higher for R32 system through comparison.

Documents disponibles

Format PDF

Pages : 7 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : A comparative study on the optimum performance of R410A and R32 refrigeration cycles.
  • Identifiant de la fiche : 30016107
  • Langues : Anglais
  • Source : Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
  • Date d'édition : 16/08/2015
  • DOI : http://dx.doi.org/10.18462/iir.icr.2015.0283

Liens


Voir d'autres communications du même compte rendu (657)
Voir le compte rendu de la conférence