Une nouvelle approche pour améliorer l'utilisation de déshydratants solides dans un lit tassé via un refroidissement intermédiaire.

A novel approach for enhancing the utilization of solid desiccants in packed bed via intercooling.

Auteurs : RAMZY A., ABDEL-MEGUID H., EL AWADY W.

Type d'article : Article

Résumé

Desiccant material in trailing layers of packed beds is not utilized effectively due to the released heat of adsorption. In this study, an intercooled packed bed is proposed to enhance the utilization of desiccant material in the trailing layers of the bed. Experimental and numerical runs are conducted for moisture adsorption processes in conventional and intercooled silica gel beds. The numerical model predicts the exit air condition with an acceptable agreement. Using intercooled bed, 22% increase in total adsorbed mass is achieved for the studied case. The optimum bed length and intercooler location are explored. Also, the effect of air flow velocity on the intercooled bed at the optimum location is presented numerically.

Détails

  • Titre original : A novel approach for enhancing the utilization of solid desiccants in packed bed via intercooling.
  • Identifiant de la fiche : 30014858
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 78
  • Date d'édition : 03/2015
  • DOI : http://dx.doi.org/10.1016/j.applthermaleng.2014.12.035

Liens


Voir d'autres articles du même numéro (19)
Voir la source