Document IIF

Une nouvelle méthode pour mesurer la puissance frigorifique d'un échangeur de chaleur à tubes ailetés.

A new method for measuring refrigerating capacity of fin-tube type heat exchanger.

Numéro : pap. ID63

Auteurs : WANG H., WATANABE M., MAN'O T., et al.

Résumé

In order to measure cooling capacity of Fin-tube type heat exchanger, a few methods have been practically used. But all of them have serious defects that worsen measuring accuracy. Authors have proposed a novel method for measuring cooling capacity which had distinct superiorities in high accuracy and brief measuring time. The method employed a duct on which test heat exchanger, electric heater and a fan were installed. The air forced to flow inside of the duct and the heater was controlled to let the
temperature inlet and outlet of the duct equal. In the room temperature experiment, the accuracy of about ±3% was obtained. The measuring accuracy, however, became totally worse when the temperature range was extended to below 0°C which was needed for preserving frozen foods. In this paper, several kinds of improvements of the measuring equipment for using at temperature below 0°C were attempted and finally ±5% in measuring accuracy was achieved.

Documents disponibles

Format PDF

Pages : 7 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : A new method for measuring refrigerating capacity of fin-tube type heat exchanger.
  • Identifiant de la fiche : 30012379
  • Langues : Anglais
  • Source : 11th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2014). Proceedings. Hangzhou, China, August 31-September 2, 2014.
  • Date d'édition : 02/08/2014

Liens


Voir d'autres communications du même compte rendu (119)
Voir le compte rendu de la conférence