Résumé
This paper presents a new fault detection and diagnosis (FDD) strategy for centrifugal chillers in building air-conditioning systems. The strategy is implemented using the fuzzy modelling and the artificial neural network techniques. Based on the sensitivity analysis of performance indices (PIs) to the chiller faults, the PI residuals between the model estimations using the normal data and the model estimations using the fault data are chosen to be normalized and to form a diagnostic classifier. The chosen PI residuals are further quantified by the proposed fuzzy models. The fault identification is realized by neural network, using the quantitative diagnostic classifier. The use of the quantitative diagnostic classifier in this FDD strategy overcomes the problem faced by classical qualitative fault classifiers when different faults have the same linguistic rule pattern. The strategy implementation is based on the data at normal and faulty operating conditions at a range of load levels and fault severity levels. The strategy is validated using the laboratory chiller data provided by ASHRAE Research Project RP-1043.
Détails
- Titre original : A novel strategy for the fault detection and diagnosis of centrifugal chiller systems.
- Identifiant de la fiche : 2010-0891
- Langues : Anglais
- Source : HVAC&R Research - vol. 15 - n. 1
- Date d'édition : 01/2009
Liens
- Liens externes :
Voir d'autres articles du même numéro (3)
Voir la source
Indexation
- Thèmes : Refroidisseurs d'eau
- Mots-clés : Refroidisseur; Anomalie; Procédé; Détection; Conditionnement d'air; Compresseur centrifuge
-
A robust fault detection and diagnosis strategy...
- Auteurs : WANG S., CUI J.
- Date : 07/2006
- Langues : Anglais
- Source : HVAC&R Research - vol. 12 - n. 3
Voir la fiche
-
Application of a generic evaluation methodology...
- Auteurs : REDDY T. A.
- Date : 09/2007
- Langues : Anglais
- Source : HVAC&R Research - vol. 13 - n. 5
Voir la fiche
-
Diagnostic d'anomalies de refroidisseurs d'eau ...
- Auteurs : ZHENG J., SUN H., ZHANG X.
- Date : 08/2007
- Langues : Chinois
- Source : HV & AC - vol. 37 - n. 201
- Formats : PDF
Voir la fiche
-
The sensitivity of chiller performance to commo...
- Auteurs : COMSTOCK M. C., BRAUN J. E., GROLL E. A.
- Date : 07/2001
- Langues : Anglais
- Source : HVAC&R Research - vol. 7 - n. 3
Voir la fiche
-
Performance evaluation of a reciprocating chill...
- Auteurs : CASTRO N. S.
- Date : 12/01/2002
- Langues : Anglais
- Source : ASHRAE Transactions. 2002 Winter Meeting, Atlantic City, New Jersey. Volume 108, part 1 + CD-ROM.
Voir la fiche