Une stratégie de contrôle séquentielle robuste pour les systèmes de traitement d'air.

A robust sequencing control strategy for air-handling units.

Auteurs : XU X., WANG S., SHI W. Z.

Type d'article : Article

Résumé

The controllers of air-handling units (AHU) should exploit split-range sequencing control strategies to determine the most economic way to use the AHU components to maintain the outlet air temperature at the set point. The control instability during the transition regions between different control modes as well as the problems in tuning the control loop(s) involving processes of different dynamic parameters are among the major difficulties when utilizing AHU sequencing control strategies in applications. A three PIs split-range sequencing control strategy with 'freezing' and gain scheduling schemes (SRFG) is developed addressing these problems. 'Freezing' means that the PI output is fixed at zero or one together with its integral term. SRFG is evaluated in various simulation tests and by comparing with conventional three PIs split-range sequencing control strategies. Test results demonstrate that SRFG strategy allows stable and robust AHU control.

Détails

  • Titre original : A robust sequencing control strategy for air-handling units.
  • Identifiant de la fiche : 2004-2955
  • Langues : Anglais
  • Source : Build. Serv. Eng. Res. Technol. - vol. 25 - n. 2
  • Date d'édition : 06/2004
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres articles du même numéro (3)
Voir la source