Une stratégie robuste de détection d'anomalies et de diagnostic pour les refroidisseurs de liquide centrifuges.

A robust fault detection and diagnosis strategy for centrifugal chillers.

Auteurs : WANG S., CUI J.

Type d'article : Article

Résumé

The paper presents a robust fault detection and diagnosis (FDD) strategy for centrifugal chillers. The strategy consists of a model-based chiller FDD scheme and a sensor fault detection, diagnosis, and estimation (FDD&E) scheme, which handle chiller faults and sensor faults, respectively. The sensor FDD&E scheme uses a PCA-based method (principal component analysis) to capture the correlations among the major measured variables in centrifugal chillers, as it performs well even in the presence of typical chiller faults. The chiller FDD scheme has been developed based on six physical performance indices, which are capable of describing the health condition of centrifugal chillers and, thus, indicating chiller faults. Only after all the sensors whose measurements are crucial to the chiller FDD are validated by the sensor FDD&E scheme is the chiller FDD scheme used to conduct the chiller system FDD. The strategy was validated using laboratory data from Ashrae RP-1043 and field data from a centrifugal chiller in a real building.

Détails

  • Titre original : A robust fault detection and diagnosis strategy for centrifugal chillers.
  • Identifiant de la fiche : 2006-2599
  • Langues : Anglais
  • Source : HVAC&R Research - vol. 12 - n. 3
  • Date d'édition : 07/2006

Liens


Voir d'autres articles du même numéro (5)
Voir la source