Résumé

In this study, an improved cooling cycle for a conventional multi-evaporators simple compression system utilizing ejector for vapour precompression is analyzed. The ejector-enhanced refrigeration cycle consists of multi-evaporators that operate at different pressure and temperature levels. A one-dimensional mathematical model of the ejector was developed using the equations governing the flow and thermodynamics based on the constant-area ejector flow model. The model includes effects of friction at the constant-area mixing chamber. The energy efficiency and the performance characteristics of the novel cycle are theoretically investigated. The comparison between the novel and conventional system was made under the same operating conditions. Also, a comparison of the system performances with environment friendly refrigerants (R-290, R-600a, R-717, R-134a, R-152a, and R-141b) is made. The theoretical results show that the COP of the novel cycle is better than the conventional system.

Documents disponibles

Format PDF

Pages : 1173-1185

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Use of ejectors in a multi-evaporator refrigeration system for performance enhancement.
  • Identifiant de la fiche : 2009-1571
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 32 - n. 6
  • Date d'édition : 09/2009

Liens


Voir d'autres articles du même numéro (39)
Voir la source