Utilisation de moteurs à commutation électronique (ECM) dans les diffuseurs d'air.

Use of electronically commutated motors (ECMs) in air terminal units.

Auteurs : KENTY K. L.

Résumé

This paper provides an overview of the ECM, specifically as it applies to an application in an air terminal unit. Comparisons of efficiencies for an ECM and traditional permanent split capacitor (PSC) motor are presented, as well as a novel relationship for the determination of a system's downstream static pressure when an ECM motor's rpm and flow rate are known. In this investigation, the ECM motor consumed less power than the PSC motor for all points examined. The cost difference for operating the ECM motor ranged from about 30% lower during high flow rate conditions to about 70% lower during turndown.

Détails

  • Titre original : Use of electronically commutated motors (ECMs) in air terminal units.
  • Identifiant de la fiche : 2009-0738
  • Langues : Anglais
  • Sujet : Technologie
  • Source : ASHRAE Transactions. 2007 Winter Meeting. Volume 113, part 1 + CD-ROM.
  • Date d'édition : 27/01/2007

Liens


Voir d'autres communications du même compte rendu (17)
Voir le compte rendu de la conférence