Ventilo-convecteur hydraulique pour les systèmes de distribution hydroniques de pointe. 1. Performance thermique et caractérisation énergétique des ventilo-convecteurs classiques.

Hydraulic-powered fan coil for advanced hydronic distribution systems. 1. Thermal performance and energy characterization of conventional fan coil units.

Résumé

The paper reports the testing of two conventional fan-coil units of different size in a controlled environment rig to determine their thermal performance and energy requirements during cooling operation. It is found that for both units, the sensible heat ratio and outlet air temperature are reduced when the water flow rate through the coil is increased and/or the fan speed is decreased. For the same inlet air and water conditions, the sensible heat ratio and outlet air temperature of the smaller fan-coil unit are lower than their counterparts of the larger unit.

Détails

  • Titre original : Hydraulic-powered fan coil for advanced hydronic distribution systems. 1. Thermal performance and energy characterization of conventional fan coil units.
  • Identifiant de la fiche : 2001-2424
  • Langues : Anglais
  • Source : ASHRAE Transactions. 2000 ASHRAE Annual Meeting, Minneapolis, Minnesota + CD-ROM.
  • Date d'édition : 24/06/2000