Document IIF
Le remplacement du R134a par le R744 : une analyse exergétique basée sur des données expérimentales.
The substitution of R134a with R744: an exergetic analysis based on experimental data.
Auteurs : APREA C., GRECO A., MAIORINO A.
Type d'article : Article, Article de la RIF
Résumé
This paper deals with the problem of R314a substitution with a natural refrigerant fluid. A comparison is performed between R134a and R744 (CO2). R134a is a hydrofluorocarbon with a large direct warming impact (GWP), whereas the R744 contribution is negligible. A comparative exergetic analysis, carried out with experimental tests, has been presented. This paper compares a commercial R134a refrigeration plant and a prototype R744 system working in a trans-critical cycle. Based on the experimental data an exergetic analysis has been carried out on the overall plant and on each device. The overall exergetic performances of the classical vapour compression plant working with R134a are consistently better than that of R744 (from a minimum of 20 to a maximum of 44%). The performance of the individual components of the plant has been analyzed, in order to pinpoint those contributing most to the decrease in the exergetic performance of R744.
Documents disponibles
Format PDF
Pages : 2148-2159
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : The substitution of R134a with R744: an exergetic analysis based on experimental data.
- Identifiant de la fiche : 30009822
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 36 - n. 8
- Date d'édition : 12/2013
Liens
Voir d'autres articles du même numéro (37)
Voir la source
Indexation
-
Thèmes :
Thermodynamique et changement d’état;
HFC;
CO2 - Mots-clés : R134a; Exergie; Application commerciale; R744; Substitut; Perte; Performance; Cycle transcritique
-
Performance optimale pour un cycle frigorifique...
- Auteurs : TAO G., CHEN L., SUN F.
- Date : 03/2008
- Langues : Chinois
- Source : Refrigeration - vol. 27 - n. 1
Voir la fiche
-
Exergy analysis of two stage cycle with an open...
- Auteurs : RUNDLE R. W., TARNAWSKI V. R., AITTOMAKI A.
- Date : 21/09/1994
- Langues : Anglais
- Source : CFCs, the Day After.
- Formats : PDF
Voir la fiche
-
Aspects thermodynamiques de la multiplication d...
- Auteurs : CHLYÂHOVETSKIJ D. V., CHLYÂHOVETSKIJ V. M.
- Date : 2002
- Langues : Russe
- Source : Vestnik Mezdunarodarnoj Akademii Holoda - n. 4
Voir la fiche
-
Considerations on transcritical CO2 systems wit...
- Auteurs : TIEDEMANN T., SÜSS J., VEJE C.
- Date : 01/09/2004
- Langues : Anglais
- Source : Compressors 2004: 5th International Conference on Compressors and Coolants
- Formats : PDF
Voir la fiche
-
Thermodynamic analysis of transcritical CO2 ref...
- Auteurs : SUN F., MA Y. T.
- Date : 05/2011
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 31 - n.6-7
Voir la fiche