Document IIF

Conseils pratiques pour l’optimisation du dégivrage.

Practical guidance for optimization of defrost.

Numéro : pap. 11

Auteurs : LOVE R. J., JEKEL T. B., REINDL D. T., et al.

Résumé

Regular defrost of air cooling coils is necessary to restore cooling performance but creates parasitic load on the refrigeration system and can result in short term temperature fluctuations in the refrigerated space. A new method that directly links defrost heat load to latent loads in the refrigerated facility and likely melt water flows is presented. Practical guidance, that is informed by both this method and measurements for actual systems, is provided for the optimization of defrost frequency and duration. Key aspects are: to have a method that terminates defrost once the coil is free of frost and there is no more melt water to avoid unproductive heating; and to vary the frequency of defrost to match the latent load the facility experiences so there is a similar frost loading at the start of each defrost.

Documents disponibles

Format PDF

Pages : 9

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Practical guidance for optimization of defrost.
  • Identifiant de la fiche : 30023351
  • Langues : Anglais
  • Source : 5th IIR International Conference on Sustainability and the Cold Chain. Proceedings: Beijing, Chine, 6-8 avril 2018
  • Date d'édition : 06/04/2018
  • DOI : http://dx.doi.org/10.18462/iir.iccc.2018.0011

Liens


Voir d'autres communications du même compte rendu (72)
Voir le compte rendu de la conférence