Amélioration de la performance d'un conditionneur d'air split grâce à un condenseur d'air refroidi par aspersion d'eau.
Improving the performance of a split-air conditioner by using an evaporatively cooled air condenser.
Auteurs : HAJIDAVALLOO E., EGHTEDARI H.
Résumé
Increasing the COP of split type home-air conditioners is a challenging problem, especially in hot weather conditions. The application of evaporatively cooled air condenser instead of commonly used air condenser is a solution to this challenge. In this paper an evaporative cooler was designed and coupled to the existing air condenser of a split air conditioner to evaluate its effect on the cycle performance under various ambient air temperatures up to 49°C. Experimental results show that application of evaporatively cooled air condenser has significant effect on performance improvement of the cycle and improvement increases as ambient air temperature increases. It is found that by using evaporatively cooled air condenser in hot weather conditions, power consumption can be reduced up to 21% and performance of the cycle can be improved up to 52%.
Documents disponibles
Format PDF
Disponible
Prix public
20 €
Prix membre*
15 €
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Improving the performance of a split-air conditioner by using an evaporatively cooled air condenser.
- Identifiant de la fiche : 2010-0191
- Langues : Anglais
- Source : Zbornik radova. 40. Medunarodni kongres o grejanju, hladenju i klimatizaciji./ Proceedings. 40th International congress on HVAC&R.
- Date d'édition : 02/12/2009
Liens
Voir d'autres communications du même compte rendu (39)
Voir le compte rendu de la conférence
Indexation
-
Application of evaporative cooling concepts to ...
- Auteurs : BROWN W. K.
- Date : 1991
- Langues : Anglais
Voir la fiche
-
Indirect evaporative cooling of a low energy bu...
- Auteurs : ARKAR C., MEDVED S., NOVAK P.
- Date : 08/1997
- Langues : Anglais
- Source : CLIMA 2000, Brussels 1997, August 30 to September 2, Congress Palace.
Voir la fiche
-
Field testing of a supervisory optimal controll...
- Auteurs : MIYAJIMA Y., SAKUMA M., SUGIURA T., et al.
- Date : 23/06/2007
- Langues : Anglais
- Source : ASHRAE Transactions. 2007 Annual Meeting, Long Beach, CA. Volume 113, part 2 + CD-ROM.
Voir la fiche
-
How to reduce the energy demand for the cooling...
- Auteurs : PAUL J.
- Date : 21/08/2007
- Langues : Anglais
- Source : ICR 2007. Refrigeration Creates the Future. Proceedings of the 22nd IIR International Congress of Refrigeration.
- Formats : PDF
Voir la fiche
-
Integrating solar radiation, building mass, the...
- Auteurs : ABAZA H., BELIVEAU Y., JONES J.
- Date : 09/07/2000
- Langues : Anglais
- Source : Air distribution in rooms: ventilation for health and sustainable environment. Roomvent 2000. Proceedings of the 7th international conference.
Voir la fiche