Expérimentation sur le terrain d'un dispositif de régulation optimisé pour un système de conditionnement d'air.
Field testing of a supervisory optimal controller for an air-conditioning system.
Auteurs : MIYAJIMA Y., SAKUMA M., SUGIURA T., et al.
Résumé
To address the growing demand for energy saving in building operation, an advanced control system for air-conditioning systems was developed and evaluated. This control system incorporates physical models of each component together with optimization engine software that enables it to calculate the optimal settings of five variables (chilled-water temperature and flow rate, condenser water temperature and flow rate, and supply air temperature) according to the current cooling (or heating) load. These setpoints are calculated to minimize the total energy consumption of the whole air-conditioning system using the optimization engine software. This paper presents an overview of the control system and the results of evaluating data obtained by applying the system to an existing building. Compared with ordinary manual operation, the system achieved energy savings of 24%.
Détails
- Titre original : Field testing of a supervisory optimal controller for an air-conditioning system.
- Identifiant de la fiche : 2008-1713
- Langues : Anglais
- Source : ASHRAE Transactions. 2007 Annual Meeting, Long Beach, CA. Volume 113, part 2 + CD-ROM.
- Date d'édition : 23/06/2007
Liens
Voir d'autres communications du même compte rendu (22)
Voir le compte rendu de la conférence
Indexation
-
Performance of a demand-limiting control algori...
- Auteurs : BRAUN J. E.
- Date : 23/06/2007
- Langues : Anglais
- Source : ASHRAE Transactions. 2007 Annual Meeting, Long Beach, CA. Volume 113, part 2 + CD-ROM.
Voir la fiche
-
Potential of energy saving by "performance insp...
- Auteurs : BERGLOF K.
- Date : 18/09/2008
- Langues : Anglais
- Source : HVAC Energy Efficiency Best Practice Conference
- Formats : PDF
Voir la fiche
-
Integrating solar radiation, building mass, the...
- Auteurs : ABAZA H., BELIVEAU Y., JONES J.
- Date : 09/07/2000
- Langues : Anglais
- Source : Air distribution in rooms: ventilation for health and sustainable environment. Roomvent 2000. Proceedings of the 7th international conference.
Voir la fiche
-
Night ventilation cooling of office buildings: ...
- Auteurs : KOLOKOTRONI M.
- Date : 2001
- Langues : Anglais
- Source : ASHRAE Transactions. 2001 Winter Meeting, Atlanta, GA. Volume 107, part 1 + CD-ROM.
Voir la fiche
-
Energy saving possibilities for cooled-ceiling ...
- Auteurs : KOOI J. van der, NIU J., DIELEMAN C. W.
- Date : 20/08/1995
- Langues : Anglais
- Source : For a Better Quality of Life. 19th International Congress of Refrigeration.
- Formats : PDF
Voir la fiche