Document IIF

Amélioration des performances de l’éjecteur de vapeur humide dans un cycle frigorifique en modifiant la géométrie de l’éjecteur à l’aide d’une nouvelle méthode basée sur la génération d’entropie, le taux d’entrainement et le coefficient de performance.

Improvement of the wet steam ejector performance in a refrigeration cycle via changing the ejector geometry by a novel EEC (Entropy generation, Entrainment ratio, and Coefficient of performance) method.

Auteurs : FOROOZESH F., BAK KHOSHNEVIS A., LAKZIAN E.

Type d'article : Article, Article de la RIF

Résumé

In this research, the improvement of an ejector performance has been studied as crucial part of an ejector refrigeration system by means of applying changes in its geometry. Water steam is taken as a non- expensive, non-toxic, and available refrigerant and wet steam model has been employed to more accurate numerical simulation and analysis. It is investigated the effect of changing geometric parameters according to the presence of wetness in the flow field. The geometric parameters are the length and diameter of the constant area section of the ejector and the diameter of primary nozzle throat. In addition to entrainment ratio (ER) and critical compression ratio (CR) of the ejector as conventional design criteria, COP of the refrigeration system and the total entropy generation (EG) in the flow inside the ejector are also used; which results in a novel EEC ( Entropy generation, Entrainment ratio, and C oefficient of performance) method for ejector design in the ejector refrigeration systems. The impact of changing each geometry parameter is examined in a separate process. Finally, the increment in the length and diameter of the constant area section and decrement in the diameter of the primary nozzle throat are considered as desirable changes. Consequently, by applying these changes ER and COP have improved by 32% and total entropy generation is decreased.

Documents disponibles

Format PDF

Pages : 248-261

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Improvement of the wet steam ejector performance in a refrigeration cycle via changing the ejector geometry by a novel EEC (Entropy generation, Entrainment ratio, and Coefficient of performance) method.
  • Identifiant de la fiche : 30027305
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 110
  • Date d'édition : 02/2020
  • DOI : http://dx.doi.org/10.1016/j.ijrefrig.2019.11.006

Liens


Voir d'autres articles du même numéro (29)
Voir la source