Analyse de fuites d'air de salles d'hôpitaux bénéficiant d'une ventilation de type particulier.

Air leakage analysis of special ventilation hospital rooms.

Auteurs : GEESLIN A., STREIFEL A.

Résumé

Hospitals use special ventilation (SPV) rooms to protect patients and employees from airborne infectious diseases. The room airtightness determines the effectiveness of the ventilation system at containing airborne infectious diseases. In this research, the authors tested SPV rooms utilizing duct pressurization equipment to determine room leakage area. The leakage testing procedure involves depressurizing the room using a fan to exhaust air out of the room at varying rates while measuring the differential pressure between the room and the adjacent corridor. Ten SPV rooms were tested and found to have significantly varying leakage areas. For airtight energy-efficient homes, the recommendation is an equivalent leakage area of 2.5 in2 per 100 ft2 of building envelope surface area (Lstiburek 2004). This study describes a method for testing room leakage area, suggests a method to trace and seal leakage sites, and makes recommendations for an airtightness standard that is achievable based on the airtightness measurements presented in this paper.

Détails

  • Titre original : Air leakage analysis of special ventilation hospital rooms.
  • Identifiant de la fiche : 2009-1253
  • Langues : Anglais
  • Source : ASHRAE Transactions. 2008 Annual Meeting, Salt Lake City, UT. Volume 114, part 2 + CD-ROM.
  • Date d'édition : 21/06/2008

Liens


Voir d'autres communications du même compte rendu (24)
Voir le compte rendu de la conférence