Air leakage analysis of special ventilation hospital rooms.
Author(s) : GEESLIN A., STREIFEL A.
Summary
Hospitals use special ventilation (SPV) rooms to protect patients and employees from airborne infectious diseases. The room airtightness determines the effectiveness of the ventilation system at containing airborne infectious diseases. In this research, the authors tested SPV rooms utilizing duct pressurization equipment to determine room leakage area. The leakage testing procedure involves depressurizing the room using a fan to exhaust air out of the room at varying rates while measuring the differential pressure between the room and the adjacent corridor. Ten SPV rooms were tested and found to have significantly varying leakage areas. For airtight energy-efficient homes, the recommendation is an equivalent leakage area of 2.5 in2 per 100 ft2 of building envelope surface area (Lstiburek 2004). This study describes a method for testing room leakage area, suggests a method to trace and seal leakage sites, and makes recommendations for an airtightness standard that is achievable based on the airtightness measurements presented in this paper.
Details
- Original title: Air leakage analysis of special ventilation hospital rooms.
- Record ID : 2009-1253
- Languages: English
- Source: ASHRAE Transactions. 2008 Annual Meeting, Salt Lake City, UT. Volume 114, part 2 + CD-ROM.
- Publication date: 2008/06/21
Links
See other articles from the proceedings (24)
See the conference proceedings
Indexing
- Themes: Comfort air conditioning
- Keywords: Tightness; Measurement; Ventilation; Air; Operating theatre; Clean room; Process; Hospital; Leakage; Air conditioning
-
Investigation of airflow and contaminant aeroso...
- Author(s) : SUN J., XI H., HUANG S.
- Date : 2006/05/21
- Languages : English
- Source: ACRA-2006. Proceedings of the 3rd Asian conference on refrigeration and air conditioning.
View record
-
Mikroorganismen in laminarer und turbulenter St...
- Author(s) : DKV, SCHEER A., FITZNER K.
- Date : 1997/11/19
- Languages : German
- Source: DKV-Tagungsbericht 24. 1997, Hamburg.
View record
-
A new idea that is 40 years old: air curtain ho...
- Author(s) : COOK G., INT-HOUT D.
- Date : 2007/01/27
- Languages : English
- Source: ASHRAE Transactions. 2007 Winter Meeting. Volume 113, part 1 + CD-ROM.
View record
-
Wirtschaftlichkeitsvergleich von Operationsraum...
- Author(s) : KÜLPMANN R., MEIERHANS R.
- Date : 2000/11/22
- Languages : German
- Source: DKV-Tagungsbericht Bremen. 2000.
View record
-
CLEAN ROOMS AND AIR CLEANING: BETTER OPERATION ...
- Author(s) : HOENIG S. A.
- Date : 1986
- Languages : English
View record