Document IIF

Analyse de la performance d'un réfrigérateur à cycle d'air muni d'un système à déshydratant, utilisé pour le refroidissement et la déshumidification d'un entrepôt.

Performance analysis of air cycle refrigerator integrated desiccant system for cooling and dehumidifying warehouse.

Auteurs : ELSAYED S. S., MIYAZAKI T., HAMAMOTO Y., et al.

Type d'article : Article, Article de la RIF

Résumé

In this paper, the performance of air cycle refrigerator integrated desiccant system used to cool and dehumidify warehouse is analyzed theoretically. Simulation analysis is carried out to calculate the system COP, cooling effects and the humidity change under different values of pressure ratio, storage zone temperature inside dock and outdoor air conditions. Also, the effect of the air cycle and the rotor parameters on the system performance is evaluated. From the simulation result it is found that, the desiccant system has the ability to supply air to the dock area at very low humidity. The system coefficient of performance increases due to the exhaust heat recovery on the desiccant system, and this enhancement can be more than 100%. The COP of the proposed system is greater than that of a conventional system under the same operating conditions.

Documents disponibles

Format PDF

Pages : 189-196

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Performance analysis of air cycle refrigerator integrated desiccant system for cooling and dehumidifying warehouse.
  • Identifiant de la fiche : 2008-0757
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 31 - n. 2
  • Date d'édition : 03/2008

Liens


Voir d'autres articles du même numéro (17)
Voir la source