Summary

In this paper, the performance of air cycle refrigerator integrated desiccant system used to cool and dehumidify warehouse is analyzed theoretically. Simulation analysis is carried out to calculate the system COP, cooling effects and the humidity change under different values of pressure ratio, storage zone temperature inside dock and outdoor air conditions. Also, the effect of the air cycle and the rotor parameters on the system performance is evaluated. From the simulation result it is found that, the desiccant system has the ability to supply air to the dock area at very low humidity. The system coefficient of performance increases due to the exhaust heat recovery on the desiccant system, and this enhancement can be more than 100%. The COP of the proposed system is greater than that of a conventional system under the same operating conditions.

Available documents

Format PDF

Pages: 189-196

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Performance analysis of air cycle refrigerator integrated desiccant system for cooling and dehumidifying warehouse.
  • Record ID : 2008-0757
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 31 - n. 2
  • Publication date: 2008/03