Analyse de performance d'un rectificateur dans une pompe à chaleur à absorption ammoniac-eau : caractéristique d'un rectificateur de type à plaque.

[In Japanese. / En japonais.]

Auteurs : TSUJIMORI A., OZAKI E., NAKAO K.

Type d'article : Article

Résumé

In this study, an experimental and analytical approach was made concerning plate-type rectifiers. In the experiment, the effect of vapour flow rate and ammonia mass concentration of solution on rectifying performance were investigated. And in the analysis the model of heat and mass transfer was proposed considering the distribution of mass concentration in the boundary layer. As a result, it was found that ammonia mass concentration at the rectifier outlet slightly decreased as vapour flow rate increased and that the model could predict ammonia mass concentration in outlet vapour for various concentrations in the solution.

Détails

  • Titre original : [In Japanese. / En japonais.]
  • Identifiant de la fiche : 1998-0872
  • Langues : Japonais
  • Source : Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers - vol. 14 - n. 1
  • Date d'édition : 1997
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres articles du même numéro (10)
Voir la source