Recommandé par l'IIF / Document IIF
Analyse expérimentale d'une pompe à chaleur haute température au R600 en fonctionnement sous-critique et trans-critique.
Experimental analysis of a R600 high-temperature heat pump in sub-critical and trans-critical operation.
Numéro : 1055
Auteurs : VERDNIK M., RIEBERER R.
Résumé
High-temperature heat pumps can provide process heat by lifting recovered waste heat to temperature levels needed for industrial processes. The application of a trans-critical cycle extends the operating range of a heat pump beyond the critical temperature of the used refrigerant.
A prototype of a high-temperature heat pump using R600 was developed and investigated. The one-stage cycle uses a suction gas cooled reciprocating compressor, a low-pressure accumulator and an internal heat exchanger (IHX) for suction gas superheating. Experimental data of sub-critical and trans-critical operation is presented. In sub-critical operation, a coefficient of performance (COP) of 4.5 at a heat source inlet temperature of 60 °C and a heat sink outlet temperature of 110 °C and in trans-critical operation a COP of 3.1 at a heat sink outlet temperature of 160 °C was achieved. The measurement data further shows a dependency of the COP on the high-side pressure and suction gas superheating realized in the IHX.
Documents disponibles
Experimental analysis of a R600 high-temperature heat pump in sub-critical and trans-critical operation
Pages : 6
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Experimental analysis of a R600 high-temperature heat pump in sub-critical and trans-critical operation.
- Identifiant de la fiche : 30027999
- Langues : Anglais
- Sujet : Technologie
- Source : 14th IIR-Gustav Lorentzen Conference on Natural Refrigerants (GL2020). Proceedings. Kyoto, Japon, December 7-9th 2020.
- Date d'édition : 07/12/2020
- DOI : http://dx.doi.org/10.18462/iir.gl.2020.1055
Liens
Voir d'autres communications du même compte rendu (120)
Voir le compte rendu de la conférence
Indexation
-
Experimental and model-based analysis of an R60...
- Auteurs : VERDNIK M., RIEBERER R.
- Date : 13/06/2022
- Langues : Anglais
- Source : 15th IIR-Gustav Lorentzen Conference on Natural Refrigerants (GL2022). Proceedings. Trondheim, Norway, June 13-15th 2022.
- Formats : PDF
Voir la fiche
-
High-temperature vapor compression heat pump us...
- Auteurs : VERDNIK M., RIEBERER R.
- Date : 31/08/2021
- Langues : Anglais
- Source : 13th IEA Heat Pump Conference 2021: Heat Pumps – Mission for the Green World. Conference proceedings [full papers]
- Formats : PDF
Voir la fiche
-
Trans-critical vapor compression cycle using bu...
- Auteurs : VERDNIK M., RIEBERER R., MOISI H.
- Date : 24/08/2019
- Langues : Anglais
- Source : Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
- Formats : PDF
Voir la fiche
-
Thermodynamic analysis of vapour compression he...
- Auteurs : ANDERSEN M. P., ZÜHLSDORF B., MARKUSSEN W. B., JENSEN J. K., POULSEN J. L., ELMEGAARD B.
- Date : 13/06/2022
- Langues : Anglais
- Source : 15th IIR-Gustav Lorentzen Conference on Natural Refrigerants (GL2022). Proceedings. Trondheim, Norway, June 13-15th 2022.
- Formats : PDF
Voir la fiche
-
Analysis of the mixture refrigerant R600/R245fa...
- Auteurs : YU X., XU C.
- Date : 31/08/2021
- Langues : Anglais
- Source : 13th IEA Heat Pump Conference 2021: Heat Pumps – Mission for the Green World. Conference proceedings [full papers]
- Formats : PDF
Voir la fiche