Recommandé par l'IIF / Document IIF

Analyse expérimentale d'une pompe à chaleur haute température au R600 en fonctionnement sous-critique et trans-critique.

Experimental analysis of a R600 high-temperature heat pump in sub-critical and trans-critical operation.

Numéro : 1055

Auteurs : VERDNIK M., RIEBERER R.

Résumé

High-temperature heat pumps can provide process heat by lifting recovered waste heat to temperature levels needed for industrial processes. The application of a trans-critical cycle extends the operating range of a heat pump beyond the critical temperature of the used refrigerant.
A prototype of a high-temperature heat pump using R600 was developed and investigated. The one-stage cycle uses a suction gas cooled reciprocating compressor, a low-pressure accumulator and an internal heat exchanger (IHX) for suction gas superheating. Experimental data of sub-critical and trans-critical operation is presented. In sub-critical operation, a coefficient of performance (COP) of 4.5 at a heat source inlet temperature of 60 °C and a heat sink outlet temperature of 110 °C and in trans-critical operation a COP of 3.1 at a heat sink outlet temperature of 160 °C was achieved. The measurement data further shows a dependency of the COP on the high-side pressure and suction gas superheating realized in the IHX.

Documents disponibles

Experimental analysis of a R600 high-temperature heat pump in sub-critical and trans-critical operation

Pages : 6

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental analysis of a R600 high-temperature heat pump in sub-critical and trans-critical operation.
  • Identifiant de la fiche : 30027999
  • Langues : Anglais
  • Sujet : Technologie
  • Source : 14th IIR-Gustav Lorentzen Conference on Natural Refrigerants (GL2020). Proceedings. Kyoto, Japon, December 7-9th 2020.
  • Date d'édition : 07/12/2020
  • DOI : http://dx.doi.org/10.18462/iir.gl.2020.1055

Liens


Voir d'autres communications du même compte rendu (120)
Voir le compte rendu de la conférence