Analyse expérimentale monophasique du transfert de chaleur dans un échangeur de chaleur à ailettes hélicoïdales.
Single-phase experimental analysis of heat transfer in helically finned heat exchanger.
Auteurs : MARTINEZ E., VICENTE W., SALINAS M., et al.
Type d'article : Article
Résumé
A methodology for designing helically serrated finned tube heat exchanger based on the logarithmic mean temperature difference method is validated with experimental tests. The method uses semi-empirical correlations for calculating convective coefficients both inside and outside staggered tube bundles. Equipment was designed, built, and installed in a paper factory in order to validate the methodology. Comparisons between predictions and experimental data show a precision of approximately 96% in heat transfer and approximately 90% in pressure drop for Reynolds numbers upper to 10,000. [Reprinted with permission from Elsevier. Copyright, 2008].
Détails
- Titre original : Single-phase experimental analysis of heat transfer in helically finned heat exchanger.
- Identifiant de la fiche : 2009-1947
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 29 - n. 11-12
- Date d'édition : 08/2009
- DOI : http://dx.doi.org/10.1016/j.applthermaleng.2008.11.002
Liens
Voir d'autres articles du même numéro (12)
Voir la source
Indexation
- Thèmes : Transfert de chaleur
- Mots-clés : Géometrie; Tube ailette; Ailette; Comparaison; Calcul; Transfert de chaleur; Experimentation; Essai; Échangeur de chaleur