Single-phase experimental analysis of heat transfer in helically finned heat exchanger.

Author(s) : MARTINEZ E., VICENTE W., SALINAS M., et al.

Type of article: Article

Summary

A methodology for designing helically serrated finned tube heat exchanger based on the logarithmic mean temperature difference method is validated with experimental tests. The method uses semi-empirical correlations for calculating convective coefficients both inside and outside staggered tube bundles. Equipment was designed, built, and installed in a paper factory in order to validate the methodology. Comparisons between predictions and experimental data show a precision of approximately 96% in heat transfer and approximately 90% in pressure drop for Reynolds numbers upper to 10,000. [Reprinted with permission from Elsevier. Copyright, 2008].

Details

  • Original title: Single-phase experimental analysis of heat transfer in helically finned heat exchanger.
  • Record ID : 2009-1947
  • Languages: English
  • Source: Applied Thermal Engineering - vol. 29 - n. 11-12
  • Publication date: 2009/08
  • DOI: http://dx.doi.org/10.1016/j.applthermaleng.2008.11.002

Links


See other articles in this issue (12)
See the source