Analyse thermique et hydraulique d'un évaporateur brasé en aluminium.

Thermal and hydraulic analysis of a brazed aluminum evaporator.

Auteurs : WU X. M., WEBB R. L.

Type d'article : Article

Résumé

This article presents an analytical/computer model to predict the performance of a brazed aluminum evaporator operating under dehumidifying conditions. This evaporator is composed of a multipan extended flat aluminium tube, linked by a lowered finned array. The programme was used to design an R404A evaporator, for which a prototype was built and tested. The programme over-predicted the evaporator capacity by 8%. The over-prediction is believed to be due to flow mal-distribution in the branch tubes.

Détails

  • Titre original : Thermal and hydraulic analysis of a brazed aluminum evaporator.
  • Identifiant de la fiche : 2003-2751
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 22 - n. 12
  • Date d'édition : 08/2002

Liens