This study optimizes a two-phase ejector cascade refrigeration system using a Particle Swarm Optimization (PSO) algorithm for low-temperature applications. The constant area analysis method identifies ejector design parameters employing refrigerants with low global warming potential (GWP), such as NH3, R290, R1234yf, and R1234ze(E). The results indicate greater exergy destruction with the R1234yf – CO2 pair, while the NH3 – CO2 pair presented the highest optimized Coefficient of Performance (COP), reaching 1.81. It is observed that an increase in ejector nozzle diameters occurs as cooling capacity increases, and nozzle efficiency also influences the variation in ejector nozzle areas and the ideal area ratio. The research demonstrates the potential of cascade cooling systems with ejectors, providing additional insights into ejector performance to achieve greater efficiency and sustainability in low-temperature applications.

Documents disponibles

Format PDF

Pages : 54-64

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Thermodynamic analysis and optimization of a modified cascade refrigeration system using two-phase ejectors and low GWP fluids.
  • Identifiant de la fiche : 30032245
  • Langues : Anglais
  • Sujet : Technologie
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 160
  • Date d'édition : 04/2024
  • DOI : http://dx.doi.org/10.1016/j.ijrefrig.2024.02.003

Liens


Voir d'autres articles du même numéro (33)
Voir la source