Application industrielle d'un refroidisseur biétagé à absorption eau-bromure de lithium.

Industrial application of a two-stage, half-effect water-lithium bromide absorption chiller.

Résumé

A 350-kilowatt two-stage, half-effect water-lithium bromide absorption chiller driven by low-temperature hot water has successfully been operated in a combined heat and power (CHP) plant in Beijing, China. This chiller can produce 9 deg C chilled water at a cooling water temperature of 32 deg C. The temperature of hot water supplied to generators can be from 75 to 86 deg C and that leaving generators is at about 60 deg C. The average chiller's COP is about 0.33 and 0.38. The paper has demonstrated that a two-stage absorption chiller is advantageous in recovering waste heat of even lower grade, as compared to a single-stage absorption chiller and that industrial application of a two-stage absorption has greater potential in recovering waste heat in various sectors of industry.

Détails

  • Titre original : Industrial application of a two-stage, half-effect water-lithium bromide absorption chiller.
  • Identifiant de la fiche : 1998-0868
  • Langues : Anglais
  • Source : Ab-sorption 96. Towards sustainable technologies. Proceedings./ Ab-sorption 96. Vers les technologies durables. Comptes rendus.
  • Date d'édition : 17/09/1996
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres communications du même compte rendu (115)
Voir le compte rendu de la conférence