Avantage en termes d'efficacité dans les conditions de charge partielle des compresseurs centrifuges sans huile à grande vitesse et entraînement direct.
The part-load efficiency benefit of oil-free, high-speed, direct-drive centrifugal compressors.
Numéro : pap. n. C10, 1349
Auteurs : ALVARES J.
Résumé
This paper will present a seasonal energy efficiency analysis of a water-cooled chiller with multiple oil-free, highspeed direct-drive centrifugal compressors and compare the results against the seasonal energy efficiency that can be expected from water-cooled chillers with screw and scroll compressors. It will be shown that the fixed built-in compression ratio of screw compressors limits the compressor efficiency at the lower-lift off-design conditions where chillers operate most of the time while the variable speed direct drive centrifugal compressor maintains its peak efficiency at off-design conditions. Following the Air-Conditioning, Heating and Refrigeration Institute (AHRI) Standard 550-590 for performance rating of water-chilling packages it will be shown that high-speed direct-drive centrifugal chillers have the capability to reduce the annual energy consumption of water-cooled chillers by more than 30% compared to typical chillers with screw compressors as a result of better compressor efficiency at off-design conditions.
Documents disponibles
Format PDF
Pages : 8 p.
Disponible
Prix public
20 €
Prix membre*
15 €
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : The part-load efficiency benefit of oil-free, high-speed, direct-drive centrifugal compressors.
- Identifiant de la fiche : 30001344
- Langues : Anglais
- Source : 2010 Purdue Conferences. 20th International Compressor Engineering Conference at Purdue.
- Date d'édition : 12/07/2010
Liens
Voir d'autres communications du même compte rendu (31)
Voir le compte rendu de la conférence
-
A centrifugal compressor cooling system using w...
- Auteurs : SUESS J.
- Date : 21/08/2016
- Langues : Anglais
- Source : 12th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2016). Proceedings. Édimbourg, United Kingdom, August 21st-24th 2016.
- Formats : PDF
Voir la fiche
-
Part load efficiency benefit of oil-free centri...
- Auteurs : ALVARES J.
- Date : 01/2015
- Langues : Anglais
- Source : Air Conditioning and Refrigeration Journal - vol. 18 - n. 1
- Formats : PDF
Voir la fiche
-
Système de conservation d'énergie appliqué aux ...
- Auteurs : HASEGAWA Y., UEDA K., MATSUO M., et al.
- Date : 03/2011
- Langues : Japonais
- Source : Refrigeration - vol. 86 - n. 1001
Voir la fiche
-
Development of one-dimensional model for initia...
- Auteurs : KUS B., NEKSÅ P.
- Date : 12/2013
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 36 - n. 8
- Formats : PDF
Voir la fiche
-
Experimental study on oil charge impact on a sc...
- Auteurs : ABOU RACHED G., RIZK J., ZOUGHAIB A., et al.
- Date : 24/08/2019
- Langues : Anglais
- Source : Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
- Formats : PDF
Voir la fiche