CARACTERISATION DU TRANSFERT DE CHALEUR D'UN ECHANGEUR DE CHALEUR A TUBES AILETES (AVEC ET SANS CONDENSATION).

HEAT TRANSFER CHARACTERIZATION OF A FINNED-TUBE HEAT EXCHANGER (WITH AND WITHOUT CONDENSATION).

Auteurs : IDEM S. A., JACOBI A. M., GOLDSCHMIDT V. W.

Type d'article : Article

Résumé

ON CONSIDERE LES EFFETS SUR LA PERFORMANCE D'UN ECHANGEUR DE CHALEUR AIR-EAU A COURANTS CROISES, A TUBES AILETES EN CUIVRE, DE LA CONDENSATION SUR LA SURFACE EXTERIEURE. ON A ESSAYE UN ECHANGEUR DE CHALEUR A DEUX PASSAGES, A QUATRE TUBES, POUR UNE PLAGE DE NOMBRES DE REYNOLDS COMPRISE ENTRE 400 ET 1.500. POUR LE FONCTIONNEMENT DE LA BATTERIE, ON A UTILISE LA CONFIGURATION DE L'ECOULEMENT A CONTRE-COURANT GLOBAL ET CELLE DE L'ECOULEMENT PARALLELE. LES COEFFICIENTS DE TRANSFERT DE CHALEUR ET DE MASSE PAR CONVECTION SONT PRESENTES DANS UN GRAPHIQUE REPRESENTANT LE FACTEUR DE COLBURN PAR RAPPORT AU NOMBRE DE REYNOLDS. LES PERTES DE PRESSION SONT PRESENTEES DANS UN GRAPHIQUE REPRESENTANT LE FACTEUR DE FROTTEMENT PAR RAPPORT AU NOMBRE DE REYNOLDS.

Détails

  • Titre original : HEAT TRANSFER CHARACTERIZATION OF A FINNED-TUBE HEAT EXCHANGER (WITH AND WITHOUT CONDENSATION).
  • Identifiant de la fiche : 1991-0123
  • Langues : Anglais
  • Source : J. Heat Transf. - vol. 112 - n. 1
  • Date d'édition : 1990