Caractéristiques de dégivrage d'une pompe à chaleur à source air-air et effets des paramètres de l'air extérieur sur la performance d'un cycle de dégivrage.
Dynamic defrosting characteristics of air source heat pump and effects of outdoor air parameters on defrost cycle performance.
Auteurs : CHEN Y. G., GUO X. M.
Type d'article : Article
Résumé
The reverse-cycle defrosting characteristics of a 11.2 kW split-type air source heat pump (ASHP) were experimentally investigated under the defrosting conditions. Based on the experimental results, the effects of outdoor air parameters on defrosting cycle performance as well as the dynamic defrosting characteristics of the ASHP unit were analyzed. The experimental results indicate that with the increase of the outdoor air relative humidity at a constant air temperature and velocity, the total power consumption, defrosting time and endotherm from indoor room during defrosting period decreased linearly, and they also decreased as the outdoor air temperature increased, but the trends of the curves presented the concave-up. The duration of the defrosting period mainly depends on the wall temperature of outdoor heat exchanger, which is corresponding to the condensing pressure during the defrosting cycle. In this paper, the concept of total COP is used to evaluate the performance of ASHP unit, and as the air temperature increased under the conditions of a fixed air relative humidity and air velocity, the total COP increased linearly, but it decreased linearly as the air relative humidity increased. [Reprinted with permission from Elsevier. Copyright, 2009].
Détails
- Titre original : Dynamic defrosting characteristics of air source heat pump and effects of outdoor air parameters on defrost cycle performance.
- Identifiant de la fiche : 2009-2153
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 29 - n. 13
- Date d'édition : 09/2009
- DOI : http://dx.doi.org/10.1016/j.applthermaleng.2009.01.003
Liens
Voir d'autres articles du même numéro (5)
Voir la source
Indexation
-
Experimental research on the reverse-cycle defr...
- Auteurs : XIAO H., ZHANG T., HUANG Y., et al.
- Date : 21/05/2006
- Langues : Anglais
- Source : ACRA-2006. Proceedings of the 3rd Asian conference on refrigeration and air conditioning.
Voir la fiche
-
Transient simulation of an air-source heat pump...
- Auteurs : LIU Z. Q., TANG G. F., ZHAO F. Y.
- Date : 22/04/2003
- Langues : Anglais
- Source : Cryogenics and refrigeration. Proceedings of ICCR 2003.
Voir la fiche
-
Étude expérimentale de l'effet du cycle inversé...
- Auteurs : WU H., XING Z., SHU P.
- Date : 04/2014
- Langues : Chinois
- Source : Journal of Refrigeration - vol. 35 - n. 156
- Formats : PDF
Voir la fiche
-
Experiment investigation of reverse cycle defro...
- Auteurs : DING Y., MA G., CHAI Q., et al.
- Date : 09/2004
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 27 - n. 6
- Formats : PDF
Voir la fiche
-
Etude et simulation d'une pompe à chaleur air-a...
- Auteurs : LIU Z. Q., TANG G. F., ZHAO F. Y.
- Date : 09/2003
- Langues : Chinois
- Source : Journal of Refrigeration - vol. 24 - n. 97
- Formats : PDF
Voir la fiche