Document IIF
Caractéristiques relatives à la performance d'un chauffe-eau au CO2 sous différentes conditions de fonctionnement.
Performance characteristics of a CO2 water heater under various operating conditions.
Numéro : pap. ID: 240
Auteurs : BAEK C. H., HEO J. H., KANG H., et al.
Résumé
An experimental study on the heating performance of a CO2 heat pump water heater was performed with the variation of operating conditions such as refrigerant charge amount, outdoor temperature, compressor frequency, EEV opening, and water mass flow rate. Based on the test results, the optimum charge amount was determined as 1600 g. At the water mass flow rates of 75 and 85 kg/h, the water heating temperatures were 67 and 60°C and the COPs were 2.55 and 2.7, respectively. In addition, the water mass flow rate and the compressor frequency were varied to maintain the water heating temperature above 60°C with a decrease in outdoor temperature. From the test results, the recommended water mass flow rate was 75 kg/h at the outdoor temperatures of 2 and -3°C, and 65 kg/h at the outdoor temperature of -8°C.
Documents disponibles
Format PDF
Pages : 7 p.
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Performance characteristics of a CO2 water heater under various operating conditions.
- Identifiant de la fiche : 30001098
- Langues : Anglais
- Source : Proceedings of the 23rd IIR International Congress of Refrigeration: Prague, Czech Republic, August 21-26, 2011. Overarching theme: Refrigeration for Sustainable Development.
- Date d'édition : 21/08/2011
Liens
Voir d'autres communications du même compte rendu (569)
Voir le compte rendu de la conférence
Indexation
-
Evaluation de l'efficacité d'un cycle de pompe ...
- Auteurs : SAIKAWA M., HASHIMOTO K.
- Date : 2001
- Langues : Japonais
- Source : Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers - vol. 18 - n. 3
Voir la fiche
-
Development and experimental analysis of CO2 he...
- Auteurs : TRINCHIERI R., NICOLANDREA C., ROVELLA P.
- Date : 21/08/2016
- Langues : Anglais
- Source : 12th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2016). Proceedings. Édimbourg, United Kingdom, August 21st-24th 2016.
- Formats : PDF
Voir la fiche
-
Toplotne pumpe za grijanje sanitarne vode sa ug...
- Auteurs : CICONKOV V., GIROTTO S., CICONKOV S.
- Date : 09/2013
- Langues : Serbe
- Source : KGH (Klimatizacija Grejanje Hladenje) - vol. 42 - n. 3
Voir la fiche
-
Mejoras en el rendimiento de los calentadores d...
- Auteurs : BOWERS C. D., ELBEL S., PETERSEN M., et al.
- Date : 11/2012
- Langues : Espagnol
- Source : Frío Calor Aire acondicionado - vol. 40 - n. 452
- Formats : PDF
Voir la fiche
-
Performance improvements in commercial heat pum...
- Auteurs : BOWERS C. D., ELBEL S., PETERSEN M., et al.
- Date : 21/08/2011
- Langues : Anglais
- Source : Proceedings of the 23rd IIR International Congress of Refrigeration: Prague, Czech Republic, August 21-26, 2011. Overarching theme: Refrigeration for Sustainable Development.
- Formats : PDF
Voir la fiche