Document IIF

Changement de composition des mélanges zéotropiques dans les zones biphasiques de circuits frigorifiques.

Shift in composition of zeotropic mixtures in two phase regions of refrigerating circuits.

Auteurs : FORNASIERI E., ZILIO C., BOBBO S., et al.

Résumé

A calculation procedure has been proposed for finding the shift from the composition of the charged refrigerant to the flow composition of the same fluid during the operation of the refrigerating circuit; this composition shift arises with zeotropic mixtures as an effect of the slip velocity between liquid and vapour during condensation and evaporation. Some diagrams are presented showing the effect of the more significant operational variables on the composition shift as well as the impact of the correlation chosen for predicting the void fraction. The composition shift occurring with the zeotropic mixtures on the market does not seem to be a problem with the current technology of refrigerating installations.

Documents disponibles

Format PDF

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Shift in composition of zeotropic mixtures in two phase regions of refrigerating circuits.
  • Identifiant de la fiche : 2000-1180
  • Langues : Anglais
  • Source : 20th International Congress of Refrigeration: Refrigeration into the Third Millennium.
  • Date d'édition : 19/09/1999

Liens


Voir d'autres communications du même compte rendu (447)
Voir le compte rendu de la conférence