Conception optimale des systèmes frigorifiques à éjecteur fonctionnant avec des frigorigènes inoffensifs sur le plan de l'environnement.

Optimum design of ejector refrigeration systems with environmentally benign fluids.

Auteurs : DAHMANI A., AIDOUN Z., GALANIS N.

Type d'article : Article

Résumé

A design methodology for simple ejector refrigeration systems of fixed cooling capacity operating with fixed temperatures of the external fluids entering the generator, the condenser and the evaporator is presented and applied for a particular combination of these four parameters. The results establish the existence of optimum values for the refrigerant pressure in the generator (P(G)) and the temperature difference in the heat exchangers (?T) which minimize the total thermal conductance of the system. These optimum values of P(G) and ?T are particularly interesting since they yield high values for the coefficient of performance and the exergetic efficiency of the system. They have been determined for four refrigerants (R134a, R152a, R290, and R600a). An objective function, which to a first approximation is proportional to the product of the capital and operational costs, is defined and used to compare the performance of the system with these refrigerants.

Détails

  • Titre original : Optimum design of ejector refrigeration systems with environmentally benign fluids.
  • Identifiant de la fiche : 30003737
  • Langues : Anglais
  • Source : International Journal of thermal Sciences - vol. 50 - n. 8
  • Date d'édition : 07/2011
  • DOI : http://dx.doi.org/10.1016/j.ijthermalsci.2011.02.021

Liens


Voir d'autres articles du même numéro (2)
Voir la source