Document IIF
Consommation énergétique des pompes à chaleur de climat froid dans différentes zones climatiques. Comparaison de systèmes mono étagé et bi-étagé.
Energy consumption of cold climate heat pumps in different climates. Comparison of single-stage and two-stage systems.
Auteurs : GSCHWEND A., MENZI T., CASKEY S., et al.
Type d'article : Article, Article de la RIF
Résumé
The aim of the study presented in this paper is the comparison of different possibilities to reduce the power consumption and environmental impact of barrack buildings of the US army. For this purpose different building standards, different heating and cooling appliances and a cold storage concept are compared using annual building simulations. These simulations are carried out for central and northern locations in the US. The focus of this paper is the applicability of cold climate heat pumps in these climates. A coupled building and appliance model has been established to allow a fair comparison based on first energy usage and CO2 emissions. Altogether seven different building configurations in six different locations have been investigated. Simulation results show the most significant energy savings (up to 90%) can be achieved by improving building insulation and heat recovery of the ventilation system. Second major improvement is the usage of two-stage heat pump systems, which drastically reduces the need for backup heating systems and lead to seasonal efficiencies (SCOPs) in the area of 3.0, or in other words an energy saving of 20–35%. Thermal storage and control concepts such as night setback in comparison show little effect. The simulation results also showed that primary energy demand or greenhouse gas emissions are better measures for the comparison of environmental impact than COP and SCOP.
Documents disponibles
Format PDF
Pages : 193-206
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Energy consumption of cold climate heat pumps in different climates. Comparison of single-stage and two-stage systems.
- Identifiant de la fiche : 30016781
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 62
- Date d'édition : 02/2016
Liens
Voir d'autres articles du même numéro (17)
Voir la source
Indexation
-
Heat pump energy efficiency performance install...
- Auteurs : HUTSON P.
- Date : 09/2008
- Langues : Anglais
- Source : IRHACE J. - vol. 20 - n. 5
Voir la fiche
-
A hybrid method to evaluate the life cycle clim...
- Auteurs : WAN H., SHEN B., LI Z., HWANG Y.
- Date : 21/08/2023
- Langues : Anglais
- Source : Proceedings of the 26th IIR International Congress of Refrigeration: Paris , France, August 21-25, 2023.
- Formats : PDF
Voir la fiche
-
Modelling of a two-stage rotary compressor.
- Auteurs : MATHISON M. M., BRAUN J. E., GROLL E. A.
- Date : 09/2008
- Langues : Anglais
- Source : HVAC&R Research - vol. 14 - n. 5
Voir la fiche
-
HSPF calculation of an economizer double-staged...
- Auteurs : BARBOUCHI S., RITZ J. B., CLODIC D.
- Date : 09/10/2008
- Langues : Anglais
- Source : Scientific symposium: industrial cooling and thermodynamic systems. The Pôle Cristal meetings. [CD-ROM + 4 DVDs]. / Colloque scientifique : froid industriel et systèmes thermodynamiques. Les rendez-vous du Pôle Cristal. [CD-ROM + 4 DVD].
- Formats : PDF
Voir la fiche
-
Experimental Setup and Test of a Desalination S...
- Auteurs : YANG S. K., SONG H. E., AHN Y. C.
- Date : 31/08/2021
- Langues : Anglais
- Source : 13th IEA Heat Pump Conference 2021: Heat Pumps – Mission for the Green World. Conference proceedings [full papers]
- Formats : PDF
Voir la fiche