Densité et température de cristallisation d'une solution aqueuse de bromure de lithium.
Density and crystallization temperature of lithium bromide aqueous solution.
Auteurs : MURAKAMI K.
Résumé
Lithium bromide aqueous solution for absorption air-conditioning systems was examined in detail with regard to its densities and crystallization temperatures. The vibratory density meter with a U-shaped tube was used for this highly precise experiment. The density of water for reliability test of this experimental set-up has a maximum deviation of 0.43 kg/m3. The minimized deviation suggests that the uncertainty of the density measurements of lithium-bromide aqueous solution would not be greater than plus or minus 0.5 kg/m3. A density correlation was developed using the data obtained. The correlation reproduces the measurement densities plus or minus 0.5%.
Détails
- Titre original : Density and crystallization temperature of lithium bromide aqueous solution.
- Identifiant de la fiche : 2006-1214
- Langues : Anglais
- Source : Green breeze from Asia: frontiers of refrigerants, heat transfer and system.. ACRA-2002. Proceedings of the Asian conference on refrigeration and air conditioning.
- Date d'édition : 04/12/2002
Liens
Voir d'autres communications du même compte rendu (50)
Voir le compte rendu de la conférence
Indexation