Density and crystallization temperature of lithium bromide aqueous solution.

Author(s) : MURAKAMI K.

Summary

Lithium bromide aqueous solution for absorption air-conditioning systems was examined in detail with regard to its densities and crystallization temperatures. The vibratory density meter with a U-shaped tube was used for this highly precise experiment. The density of water for reliability test of this experimental set-up has a maximum deviation of 0.43 kg/m3. The minimized deviation suggests that the uncertainty of the density measurements of lithium-bromide aqueous solution would not be greater than plus or minus 0.5 kg/m3. A density correlation was developed using the data obtained. The correlation reproduces the measurement densities plus or minus 0.5%.

Details

  • Original title: Density and crystallization temperature of lithium bromide aqueous solution.
  • Record ID : 2006-1214
  • Languages: English
  • Source: Green breeze from Asia: frontiers of refrigerants, heat transfer and system.. ACRA-2002. Proceedings of the Asian conference on refrigeration and air conditioning.
  • Publication date: 2002/12/04

Links


See other articles from the proceedings (50)
See the conference proceedings