Document IIF

Développement d'un système mixte de conditionnement d'air et de chauffage d'eau fonctionnant à l'aide d'un cycle transcritique au CO2.

Development of simultaneous air-conditioning and water heating system using CO2 transcritical cycle.

Résumé

A test rig of a CO2 system providing refrigeration for producing chilled water and hot water simultaneously has been built in ITB, Indonesia. This paper discusses design aspects and several experimental results. The test rig consists of a CO2 circuit, hot water and chilled water loops, and three indoor units. For 57 °C hot water temperature and 13 °C inlet air temperature to the conditioned rooms, total-COP is 4.2 and cooling-COP is 2.5. A higher COP could be expected if the test rig equipped with proper internal heat exchanger which is ineffective at the moment. The system seems to be one of attractive alternatives in the Indonesian refrigeration market.

Documents disponibles

Format PDF

Pages : 2004-2

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Development of simultaneous air-conditioning and water heating system using CO2 transcritical cycle.
  • Identifiant de la fiche : 2005-2761
  • Langues : Anglais
  • Source : Natural Working Fluids 2004: 6th IIR-Gustav Lorentzen Conference
  • Date d'édition : 01/08/2004

Liens


Voir d'autres communications du même compte rendu (105)
Voir le compte rendu de la conférence