Document IIF

Développement de l'éthanol dans les systèmes à fluide secondaire.

Development of ethanol secondary refrigerant system.

Auteurs : NISHIDA K., SATO H., SANO M.

Résumé

Ethanol secondary refrigerant, which consists of an ethanol solution and corrosion inhibitors, has low viscosity and low environmental influence. It is therefore useful in constructing harmless systems to the environment and low energy consumption systems. Ethanol secondary refrigeration system performance tests under the condition close to the actual used, were carried out at various conditions. As a result, it was found no specific corrosion nor seal problems. It was found that the total cost of ethanol secondary refrigeration system is the most economical system at low temperatures around less than 35 °C.

Documents disponibles

Format PDF

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Development of ethanol secondary refrigerant system.
  • Identifiant de la fiche : 2000-1370
  • Langues : Anglais
  • Source : 20th International Congress of Refrigeration: Refrigeration into the Third Millennium.
  • Date d'édition : 19/09/1999

Liens


Voir d'autres communications du même compte rendu (447)
Voir le compte rendu de la conférence