Document IIF

Développement et essai du remplacement du R12 par un fluide à ODP nul, dans les compresseurs centrifuges.

Development and testing of a zero ODP replacement for R12 in centrifugal compressors.

Résumé

The paper describes how a drop-in replacement for R12 for use in centrifugal compression refrigerating system was developed and tested. The method was to blend components of higher molecular weight than R12 with R134a in such proportions that the pressure-temperature relationship of the blend was similar to that of R12 and the molecular weight of the blend was about 121. A suitable blend has been commercialised.

Documents disponibles

Format PDF

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Development and testing of a zero ODP replacement for R12 in centrifugal compressors.
  • Identifiant de la fiche : 2000-1295
  • Langues : Anglais
  • Source : 20th International Congress of Refrigeration: Refrigeration into the Third Millennium.
  • Date d'édition : 19/09/1999

Liens


Voir d'autres communications du même compte rendu (447)
Voir le compte rendu de la conférence