Distribution de l'air et régulation de la température dans les salles de classe.

Air distribution and temperature control in classrooms.

Auteurs : KURNITSKI J., AALTO M.

Résumé

Air distribution solutions for classrooms aiming to lower air velocities and good temperature control are studied by measurements in 6 schools and temperature simulations. Air velocity measurements showed good performance of duct and ceiling diffusers which provided maximum velocities less than 0.2 m/s and can be highly recommended for classrooms. The wall diffusers were clearly not suitable for classrooms due to high velocities up to 0.43 m/s. Displacement ventilation diffusers were very sensitive to supply air temperature, as with the temperature difference of 3°C velocities up to 0.28 m/s were measured. Room temperature measurement results showed a typical problem with temperature control as at the end of the heating season the temperatures up to 25°C were measured. The parametric simulations showed that high supply air flow rates up to 10 L/s per person and cool supply air down to 14-15°C were needed for room temperature control.

Détails

  • Titre original : Air distribution and temperature control in classrooms.
  • Identifiant de la fiche : 2008-2685
  • Langues : Anglais
  • Source : Clima 2007. WellBeing Indoors. Proceedings of the 9th REHVA World Congress [CD-ROM + Abstract book].
  • Date d'édition : 10/06/2007

Liens


Voir d'autres communications du même compte rendu (76)
Voir le compte rendu de la conférence